1/16 DIN

Resources

Manufacturers

    PM6C1EK-AAAAAAA 1/16-DIN 2-Outputs

    PM6C1EK-AAAAAAA

    New

    • Replacement for Watlow 965A-3DK0-00RR
    • One Universal Input Provides Flexibility
    • Output#1 5A Mechanical Relay (Form C)
    • Output #2 0.5A Solid State Relay (Form A)
    • Operating Voltage 85 ~ 264Vac
    • Auto-Tune PID Controller
    • Also Available In 12 ~ 40Vdc Or 20 ~ 28Vac Model PM6C3EK-AAAAAAA

    More details

    $262.00

    Shipping Rates

    5 Items Available

    • Electro-Mechanical Relay Form C Specifications:

      • Maximum Resistive Load 5A at 240Vac Or 30Vdc
      • 20mA at 24V Minimum Load
      • Rated For Pilot Duty 125Va at 120/240Vac And 25Va at 24Vac
      • Single Pole Double Throw Normally Open Contact
      • 100,000 Cycles at Rated Load
      • Output Does Not Supply Power
      • For Use On AC Or DC Loads

      Solid State Relay Form A Specifications:

      • Maximum Resistive Load 0.5A at 20 ~ 264Vac
      • Rated For Pilot Duty 20Va 120/240Vac
      • Single Pole Single Throw Normally Open Contact
      • Opto Isolated Without Contact Suppression
      • Off State Leakage Maximum 105mA
      • Output Does Not Supply Power
      • Not For Use On DC Loads

      Two Wire Bus Communication Interface Type EIA-485 Also Known As RS-485 Comes Standared With All PM Series Controllers Which Can Provide An Easy Alternative to Setting Up Program Menu Options. Various Profiles Can Be Configured And Saved As Files And Can Be Up Loaded To Other PM Controllers. USB To Serial Converter Is Required To Connect The PM Controller To Any Computer With A USB Port.

      NOTE: Switching Pilot Duty Devices Such As Control Coils For Relays Or Contactors Produces An Electro-Magnetic Force When De-Engergizing Those Type Of Loads. To Protect The Controller's Electronic Circuitry From The Inductive User Load, The Use Of An RC Suppressor Also Known As A Snubber Device Should Be Wired Between The Load And The Load Output Terminal Of The Controller. An Exception Is The Use Of Watlow Solid State Relays Having Internal RC Suppression.

      Review The Data Sheet Tab For More Specifics Or Check Out The Operator's Manual From The Download Tab

      PROGRAM FEATURESAdvanced Auto-Tune PID Control Algorithm
      AGENCY APPROVALSUL Listed, CSA, CE, RoHS, W.E.E.E. FM
      WARRANTY Three Years
      OTHER FEATURESIP2X Increases Safety For Installers And Operators
        What is the difference between model numbers ending in BAA and models ending in AAA?
        Both controllers have the same form, fit, and function in fact they are the same controller with the exception of the program menus. The PM controllers ending in BAA have a more user-friendly EXPRESS menu that is application-oriented for thermal control. The PM controllers ending in AAA have a more comprehensive menu that in addition to thermal control the programming of various other processes such as pressure, humidity, valve control and much more is included in the programing menu.

        What is the difference between model numbers beginning with the letter B or A after the first dash?
        The 1/16th DIN Watlow EZ-Zone PM controllers beginning with the letter B after the first dash have blue tooth communication capability. The blue tooth is user selected on or off and there is no extra charge for this feature. Blue tooth allows viewing or programing the controller via a smart phone or blue tooth enabled pad using Watlow's EZ-Link software available free from Apple's app/store or the Google/play store. The 1/16th DIN Watlow EZ-Zone PM controllers beginning with the letter A after the first dash have standard serial bus capability allowing RS-485 2-wire to USB communication using the same Watlow EZ-Link free software together with a serial to USB accessory connector purchased seperatly.

    Accessories