1/16 DIN

Resources

Manufacturers

    PM6C3CA-AAAAAAA 1/16-DIN 1-Output

    PM6C3CA-AAAAAAA

    New

    Replacement for Watlow 965A-3CA1-00RR

    • One Universal Input Provides Flexibility
    • Single Output Either Switched DC  Or DC Open Collector
    • Operating Voltage 12 ~ 40vDc  Or  20 ~ 28Vac 
    • Auto-Tune PID Controller With Extensive Menu Options
    • Available In 85 ~ 264Vac Model PM6C1CA-AAAAAAA

    More details

    $242.00

    Shipping Rates

    2 Items Available

    • Switched DC Specifications:

      • 30mA DC Maximum Supply Current
      • Short Circuit Limited to < 50mA
      • 22 ~ 32V -DC Open Circuit Voltage
      • Drives External Relay Using dc- and dc+

      Open Collector Specifications:

      • Current Sinking Output @ 100mA Maximum
      • Maximum Supply Voltage -30Vdc
      • For DC Loads An External Power Supply Is Required
      • Connect Load Negative To Open Collector


      Two Wire Bus Communication
      Interface Type EIA-485 Also Known As RS-485 Comes Standared With All PM Series Controllers Which Can Provide An Easy Alternative to Setting Up Program Menu Options.  Various Profiles Can Be Configured And Saved As Files And Can Be Up Loaded To Other PM Controllers. USB To Serial Converter Is Required To Connect The PM Controller To Any Computer With A USB Port. 

      NOTE: Switching Pilot Duty Devices Such As Control Coils For Relays Or Contactors Produces An Electro-Magnetic Force When De-Engergizing Those Type Of Loads.  To Protect The Controller's Electronic Circuitry From The Inductive User Load, The Use Of An RC Suppressor Also Known As A Snubber Device Should Be Wired Between The Load And The Load Output Terminal Of The Controller.  An Exception Is The Use Of Watlow Solid State Relays Having Internal RC Suppression.

      Review The Data Sheet Tab For More Specifics Or Check Out The Operator's Manual From The Download Tab

      PROGRAM FEATURESAdvanced Auto-Tune PID Control Algorithm
      AGENCY APPROVALSUL Listed, CSA, CE, RoHS, W.E.E.E. FM
      WARRANTY Three Years
      OTHER FEATURESIP2X Increases Safety For Installers And Operators
        What is the difference between model numbers ending in BAA and models ending in AAA?
        Both controllers have the same form, fit, and function in fact they are the same controller with the exception of the program menus. The PM controllers ending in BAA have a more user-friendly EXPRESS menu that is application-oriented for thermal control. The PM controllers ending in AAA have a more comprehensive menu that in addition to thermal control the programming of various other processes such as pressure, humidity, valve control and much more is included in the programing menu.

        What is the difference between model numbers beginning with the letter B or A after the first dash?
        The 1/16th DIN Watlow EZ-Zone PM controllers beginning with the letter B after the first dash have blue tooth communication capability. The blue tooth is user selected on or off and there is no extra charge for this feature. Blue tooth allows viewing or programing the controller via a smart phone or blue tooth enabled pad using Watlow's EZ-Link software available free from Apple's app/store or the Google/play store. The 1/16th DIN Watlow EZ-Zone PM controllers beginning with the letter A after the first dash have standard serial bus capability allowing RS-485 2-wire to USB communication using the same Watlow EZ-Link free software together with a serial to USB accessory connector purchased seperatly.