SCR Contactors

Resources

Manufacturers

    DB10-60C0-0000 Watlow Din-A-Mite B

    DB10-60C0-0000

    New

    • Line Voltage 277~600Vac 1-Phase
    • Control Voltage 4.5~32Vdc
    • 8mA Maximum Control Current @4.5Vdc
    • Din Rail Mount or Flat Panel Mounting
    • Back to Back SCR Design
    • Zero Cross Switching Up-To 40A@77°F thru 104°F (see table below)
    • Available with Shorted SCR Alarm Watlow DB10-60C0-S000

    More details

    $165.00

    Shipping Rates

    3 Items Available

    • Din-A-Mite B Current De-Ratings Shown Are Based On Natural Convection

                          176°F....20-Amp          158°F....25-Amp        140°F....30-Amp      122°F....35-Amp

      Din-A-Mite B  Operator Interface

      • Control input and indication light
      • Alarm output and indication light

       

      Din-A-Mite B  Operating Environment

      • 0 to 90% non-condensing relative humidity
      • Storage temperature: -40°F to 185°F(-40°c to 85°c)
      • Operating temperature: -29°F to 176°F(-34°c to 80°c)
      • Insulation tested to 3,000 meters

       

      Din-A-Mite B  Terminals

      • Control input terminals: compression 24 to 16 AWG max torque 4.4 in/lb
      • Line & Load terminals: compression 14 to 4 AWG max torque 24 in/lb

       

      Din-A-Mite B  Mounting & Dimensions

      • DIN-Rail 35mm X 7.5mm DIN EN 50022
      • Back-Panel four mounting holes #6 to #8 fastener size
      • 3.7"H x 3.3"W x 4.9"D 1.5/Lb.s

       

      Din-A-Mite B  Agency Approvals

      • CE with proper filter: 204/108/EC electromagnetic compatibility directive EN 61326-1: industrial immunity Class A emissions not suitable for Class B environments, 2006/95/EC low voltage directive EN50178 safety requirements installation category III, pollution degree 2.
      • UL-508 listed
      • C-UL file E73741