• Bottom Flange = 31" Square
  • Roof Opening = 24" Square
  • Curb Height = 12"
  • Made In The USA
  •  

    ">

    1/16 DIN

    Recursos

    Fabricantes

      PM6C3EC-AAAAAAA 1/16-DIN 2-Outputs

      PM6C3EC-AAAAAAA

      New

      • Replacement for Watlow 965A-3DC1-00RR
      • One Universal Input Provides Flexibility
      • Output#1 5A Mechanical Relay (Form C)
      • Output#2 Either Switched DC Or DC Open Collector
      • Operating Voltage 12 ~ 40Vdc Or 20 ~ 28Vac
      • Auto-Tune PID Controller With Extensive Menu Options
      • Also Available In 85 ~ 264Vac Model PM6C1EC-AAAAAAA

      For "How To" Videos and More Information Visit Google+ Plus

      More details

      $253.00

      Tarifas de envío

      2 Items

      • Electro-Mechanical Relay Form C Specifications:

        • Maximum Resistive Load 5A at 240Vac Or 30Vdc
        • 20mA at 24V Minimum Load
        • Rated For Pilot Duty 125Va at 120/240Vac And 25Va at 24Vac
        • Single Pole Double Throw Normally Open Contact
        • 100,000 Cycles at Rated Load
        • Output Does Not Supply Power
        • For Use On AC Or DC Loads

        Switched DC Specifications:

        • 30mA DC Maximum Supply Current
        • Short Circuit Limited to < 50mA
        • 22 ~ 32V -DC Open Circuit Voltage
        • Drives External Relay Using dc- and dc+

        Open Collector Specifications:

        • Current Sinking Output @ 100mA Maximum
        • Maximum Supply Voltage -30Vdc
        • For DC Loads An External Power Supply Is Required
        • Connect Load Negative To Open Collector

        Two Wire Bus Communication Interface Type EIA-485 Also Known As RS-485 Comes Standared With All PM Series Controllers Which Can Provide An Easy Alternative to Setting Up Program Menu Options. Various Profiles Can Be Configured And Saved As Files And Can Be Up Loaded To Other PM Controllers. USB To Serial Converter Is Required To Connect The PM Controller To Any Computer With A USB Port.

        NOTE: Switching Pilot Duty Devices Such As Control Coils For Relays Or Contactors Produces An Electro-Magnetic Force When De-Engergizing Those Type Of Loads. To Protect The Controller's Electronic Circuitry From The Inductive User Load, The Use Of An RC Suppressor Also Known As A Snubber Device Should Be Wired Between The Load And The Load Output Terminal Of The Controller. An Exception Is The Use Of Watlow Solid State Relays Having Internal RC Suppression.

        Review The Data Sheet Tab For More Specifics Or Check Out The Operator's Manual From The Download Tab

        PROGRAM FEATURESAdvanced Auto-Tune PID Control Algorithm
        AGENCY APPROVALSUL Listed, CSA, CE, RoHS, W.E.E.E. FM
        WARRANTY Three Years
        OTHER FEATURESIP2X Increases Safety For Installers And Operators